n045
Frequency LED LCD 0 or 1 0 5.14
Reference Setting
Setting
Description
Retention 0 Memorize FREF**Retained in Frequency
Reference 1 (
n024
)
(MOP Ref (for Up/Down, Sample/
Memory) Hold functions)
1 Not Memorized Not retained
n046
Frequency LED LCD 0 or 1 0 5.13
Reference Setting
Setting Description
Loss Detection 0 Not Detected ** No detection
(Ref Loss 1 RUN @ no47 Fref Continue to run at
Detect) value set in
n047
n047
Freq. Ref. Level 0 to 100 80 (%) 5.13
at loss of Freq.
detection
(Fref Lvl@F
Loss)
n048
Terminal FV 0 to 200 100 (%) 5.10
Gain
(Terminal FV
Gain)
See Note 5
n049
Terminal FV –100 0 (%) 5.10
Bias to
(Terminal FV 100
Bias)
See Note 5
n050
Terminal FI 0 to 200 100 (%) 5.10
Gain
(Terminal FI
Gain)
n051
Terminal FI -100 0 (%) 5.10
Bias to 100
(Terminal FI
Bias)
n052
Multi-function LED LCD 0 to 3 0 5.18
Analog Output Setting
Setting Monitor
0 Output Freq ** Output frequency (Hz)
(Terminal AM 1 Output Amps Output current (A)
Sel) 2 Output kWatts Output power (kW)
3 DC Bus Voltage DC bus voltage (VDC)
n053
Analog Monitor 0.01 1.00 5.18
Gain to 2.00
(Terminal AM
Gain)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.
A1-7