n054
Carrier LED LCD 1 to 9
See Note 3
5.5
Frequency Setting
Setting 1 (x2.5 khz) 2.5 kHz
(Carrier Freq 2 (x2.5 khz) 5.0 kHz
Sel) 3 (x2.5 khz) 8.0 kHz
4 (x2.5 khz) 10.0 kHz
5 (x2.5 khz) 12.5 kHz
6 (x2.5 khz) 15.0 kHz
7 Synchronous 1
8 Synchronous 2
9 Synchronous 3
10 7.0 kHz
(6)
n055
Momentary LED LCD 0 to 2 0 5.17
Power Loss Setting
Setting
Description
Ride-through 0 Not Provided ** Not provided
Method 1 2 Seconds Max Continuous operation after
power recoverywithin 2 sec.
(PwrL 2 CPU Power Active Continuous operation after
Selection) power recovery within cont-
rol logic time (no fault output)
n056
Speed Search 0 to 200 110 (%) 5.19E
Operation
Level
(SpdSrch
Current)
n057
Minimum Base 0.5 to 5.0 (Sec) 5.19E
Block Time
(Min
See Note 3
Baseblock t)
n058
V/f Reduction 0 to 100 (%) 5.19E
Level During
Speed Search
See Note 3
(SpdSrch V/F)
n059
Momentary 0.0 to 2.0 (Sec) 5.17
Power Loss
Ride-through
See Note 3
Time
(PwrL
Ridethru t)
n060
Number of 0 to 10 0 5.4
Automatic
Restart
Attempts
(Num of
Restarts)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.