n061
Fault Contact LED LCD 0 or 1 0 5.4
Selection at Setting
Setting Description
Automatic 0
Activate Flt Rly**
Closed during
Restart auto restart
1 No Rly Output Open during
(Restart Sel) auto restart
n062
Prohibit 0.0 0.0 (Hz) 5.6
Frequency 1 to 400.0
(Jump Freq 1)
n063
Prohibit 0.0 0.0 (Hz) 5.6
Frequency 2 to 400.0
(Jump Freq 2)
n064
Prohibit 0.0 to 25.5 1.0 (Hz) 5.6
Frequency
Deadband
(Jump
Bandwidth)
n065
Elapsed Timer LED LCD 0 or 1 1
Selection Setting
Setting Description
0 Time Power is ON Accumulated time
during power on
(Elapsed 1
Time Running Mtr**
Accumulated time
Timer) during running
n066
Elapsed Used to set an initial value 0 to 9999 0 (Hours)
Timer 1 into the elapsed time meter.
(Elapsed
Time 1)
n067
Elapsed Used to set an initial value 0 to 27 0
Timer 2 into the elapsed time meter. (x 10,000)
(Elapsed hours)
Time 2)
n068
DC Injection 0 to 100 50 (%) 5.7
Current
[100% = drive
(DCInj Current)
rated current]
n069
DC Injection 0.0 to 10.0 0.0 (Sec) 5.7
Time at Stop
(DCInj Time@
Stop)
n070
DC Injection 0.0 to 10.0 0.0 (Sec) 5.7
Time at Start
(DCInj Time@
Start)
Table A1-1. Drive Parameters (
nXXX
) – Continued
PARAM.
FUNCTION NAME SETTING FACTORY USER PARA.
NO. (ACTUAL DISPLAY)
DESCRIPTION
RANGE SETTING ** SETTING REF.
A1-9