6.6 Peripheral Devices and Options
166 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
A - Shield
B - Sheath
C - Insulate with electrical tape or shrink tubing.
Figure 6.1 Prepare the Ends of Shielded Wire
â–  Prepare Network Cables for Non-LonWorks Options
Determine the length of cable required to connect from the option to a network device and attach all connectors to
network cables before you install the option.
The network connection point on the option is designated CN1. CN1 may have 2 ports depending on the option type.
CN1 is the connection point for a customer-supplied network cable with a modular RJ45 connector.
Table 6.10 8-Way Modular Connector (Customer-Supplied)
Male 8-Way Modular Connector Pin Description
1 (Pair 2) Transmit data (TXD) +
2 (Pair 2) Transmit data (TXD) -
3 (Pair 3) Receive data (RXD) +
4 (Pair 1) Not used for 10 Mbps and 100 Mbps networks
5 (Pair 1) Not used for 10 Mbps and 100 Mbps networks
6 (Pair 3) Receive data (RXD) -
7 (Pair 4) Not used for 10 Mbps and 100 Mbps networks
8 (Pair 4) Not used for 10 Mbps and 100 Mbps networks
Communication Protocol Description
EtherNet/IP
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IPâ„¢). Using a cable not specifically recommended may
cause the option or bypass to malfunction. Refer to the ODVA website for more information on network cabling (www.odva.org).
Modbus TCP/IP
Only use cable recommended for Modbus TCP/IP. Using a cable not specifically recommended may cause the option or bypass to
malfunction. Refer to the Modbus-IDA website for more information on network cabling (www.modbus.org).
PROFINET
Only use cable recommended for PROFINET. Using a cable not specifically recommended may cause the option or bypass to
malfunction. Refer to the PROFIBUS and PROFINET International (PI) website for more information (www.profibus.com).
â–  Install the Option
1. Remove the bypass cover.
2. Put the option into port CN5 on the bypass PCB.
Latch release
1 2 3 4 5 6 7 8