Parameter List
7
7.8 H: Terminal Functions
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 199
No.
(Hex.)
Name Description
Default
(Range)
H2-64
(1B4A)
Expert
Terminal M3-M4 Logical
Operation
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection] and H2-
63 [Term M3-M4 Secondary Function].
0
(0 - 8)
H2-65
(1B4B)
Expert
Terminal M3-M4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M3-M4. 0.1 s
(0.0 - 25.0 s)
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Terminal M5-M6 Function Select].
F
(0 - FF)
H2-67
(1B4D)
Expert
Terminal M5-M6 Logical
Operation
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection] and H2-
66 [Term M5-M6 Secondary Function].
0
(0 - 8)
H2-68
(1B4E)
Expert
Terminal M5-M6 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M5-M6. 0.1 s
(0.0 - 25.0 s)
H2-xx: MFDO Setting Values
Setting Value Function Description
0 During Run The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
1 Zero Speed The terminal activates when the output frequency < E1-09 [Minimum Output Frequency].
ON : Output frequency < E1-09.
OFF : Output frequency E1-09.
2 Speed Agree 1 The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of frequency reference ± L4-02.
OFF : The output frequency does not align with the frequency reference although the drive is running.
3 User-Set Speed Agree 1 The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse
detection level.
ON : The output frequency is in the range of L4-01 ± L4-02 and the range of frequency reference ± L4-02.
OFF : The output frequency is not in the range of L4-01 ± L4-02 or the range of frequency reference ± L4-02.
4 Frequency Detection 1 The terminal deactivates when the output frequency > L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection
Width]. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse
detection level.
ON : The output frequency < L4-01, or the output frequency L4-01 + L4-02
OFF : The output frequency > L4-01 + L4-02
5 Frequency Detection 2 The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal activates, the terminal
stays activated until the output frequency is at the value of L4-01 - L4-02 [Speed Agree Detection Width].
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse
detection level.
ON : The output frequency > L4-01
OFF : The output frequency < L4-01 - L4-02, or the output frequency L4-01
6 Drive Ready The terminal activates when the drive is ready and running.
7 DC Bus Undervoltage The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in L2-05 [Undervoltage
Detection Lvl (Uv1)] or less. The terminal also activates when there is a fault with the DC bus voltage.
ON : The DC bus voltage L2-05
OFF : The DC bus voltage > L2-05
8 During Baseblock (N.O.) The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.