7.8 H: Terminal Functions
198 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Setting Value Function Description
188 !Thermostat Fault Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is OFF.
Note:
This function is active when the drive is running.
1A8
!PI2 Control Disable Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the output
performance.
ON : Disabled
OFF : Enabled
â—† H2: Digital Outputs
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
0
(0 - 1FF)
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through
mode.
1
(0 - 1FF)
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
Note:
When you do not use this terminal, or when you will use the terminal in through mode, set this
parameter to F.
2
(0 - 1FF)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal. 0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal. 0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal. 0001
(0001 - 1FFF)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal. 0000
(0000 - FFFF)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.). F
(0 - 1FF)
H2-60
(1B46)
Expert
Term M1-M2 Secondary
Function
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals
assigned to functions by H2-01 [Term M1-M2 Function Selection].
F
(0 - FF)
H2-61
(1B47)
Expert
Terminal M1-M2 Logical
Operation
Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection] and H2-
60 [Term M1-M2 Secondary Function].
0
(0 - 8)
H2-62
(1B48)
Expert
Terminal M1-M2 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M1-M2. 0.1 s
(0.0 - 25.0 s)
H2-63
(1B49)
Expert
Term M3-M4 Secondary
Function
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals
assigned to functions by H2-02 [Term M3-M4 Function Selection].
F
(0 - FF)