Parameter List
7
7.8 H: Terminal Functions
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 207
Setting Value Function Description
1F Not Used Use this setting for unused terminals or to use terminals in through mode.
24 PID Feedback Backup Enters the PID Feedback Backup signal for the drive to use when it loses the primary PID feedback set for H3-xx = B [PID
Feedback].
Note:
The full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
25
PI2 Control Setpoint Enters the PI2 Control setpoint level as a percentage of the S3-02 [PI2 Control Transducer Scale] value.
Note:
Parameters S3-03 [PI2 Control Decimal Place Pos] and S3-04 [PI2 Control Unit Selection] set the resolution and unit.
26
PI2 Control Feedback Enters the PI2 Control feedback level as a percentage of the S3-02 [PI2 Control Transducer Scale] value.
Note:
Parameters S3-03 [PI2 Control Decimal Place Pos] and S3-04 [PI2 Control Unit Selection] set the resolution and unit.
27
PI Auxiliary Control
Feedback
Enters the PI Auxiliary Control feedback value when YF-01 = 1 [PI Aux Control Selection = Enabled].
Note:
• The full-scale of the analog signal goes from 0% to YF-02 [PI Aux Control Transducer Scale].
• Parameter YF-22 [PI Aux Level Decimal Place Pos] sets the resolution.
2B
Emergency Override PID
Feedback
This input is the PID Feedback source when Emergency Override is running in PID mode (S6-02 = 2 or 3 [Emergency Override Ref
Selection = System PID Mode or Independent PID Mode]).
Note:
• When S6-02 = 2 [Emergency Override Ref Selection = System PID Mode], the full-scale of the analog signal goes from b5-71
[Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
• When S6-02 = 3 [Independent PID Mode], the full-scale of the analog signal goes from b5-71 to S6-03 [EMOVR Independent
PID Scale].
• When you set MEMOBUS register 3A93h bit 4, register 3A95h becomes the Emergency Override Feedback source.
2C
Emergency Override PID
Setpoint
This input is the PID Setpoint source when Emergency Override is running in PID mode (S6-02 = 2 or 3 [Emergency Override Ref
Selection = System PID Mode or Independent PID Mode]).
Note:
• When S6-02 = 2 [Emergency Override Ref Selection = System PID Mode], the full-scale of the analog signal goes from b5-71
[Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
• When S6-02 = 3 [Independent PID Mode], the full-scale of the analog signal goes from b5-71 to S6-03 [EMOVR Independent
PID Scale].
• When you set MEMOBUS register 3A93h bit 5, register 3A96h becomes the Emergency Override Setpoint source.
2D
Differential Level Source Enters a feedback value to calculate the Differential Level between the Differential Level Source feedback and the primary PID
Feedback [H3-xx = B].
Note:
The full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
2E
HAND Frequency Ref or
Setpoint
Enters the S5-05 [HAND Frequency Reference] value or the S5-06 [HAND Setpoint] value. When S5-01 = 0 [HAND Frequency
Reference Source = HAND Analog Input] and S5-03 = 0 [HAND Mode PI Selection = Disabled], the drive enters HAND
Frequency Reference. When b5-01 ≠0, S5-01 = 0, and S5-03 = 1 [Enabled], the drive enters HAND Setpoint.
Note:
• When PID is enabled, the full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User
Unit Display Scaling].
• When PID is disabled, the drive enters this analog signal as the percentage of the E1-04 [Maximum Output Frequency] value.
â—† H4: Analog Outputs
No.
(Hex.)
Name Description
Default
(Range)
H4-01
(041D)
Terminal FM Analog Output
Select
Sets the monitor number to send from MFAO terminal FM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02 [Output
Frequency].
102
(000 - 999)
H4-02
(041E)
RUN
Terminal FM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when an output
for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
H4-03
(041F)
RUN
Terminal FM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when an output
for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03 [Output
Current].
103
(000 - 999)
H4-05
(0421)
RUN
Terminal AM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output level from
the AM terminal at 10 Vor 20 mA as 100%.
50.0%
(-999.9 - +999.9%)