7.8 H: Terminal Functions
208 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
No.
(Hex.)
Name Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output level from
the AM terminal at 10 Vor 20 mA as 0%.
0.0%
(-999.9 - +999.9%)
H4-07
(0423)
Terminal FM Signal Level
Select
Sets the MFAO terminal FM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-08
(0424)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
0
(0, 2)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when you set U1-08 [Output Power] for analog output. 0.00 kW
(0.00 - 650.00 kW)
â—† H5: Serial Communication
No.
(Hex.)
Name Description
Default
(Range)
H5-01
(0425)
Drive Node Address Sets the communication slave address for drives.
Note:
• Restart the drive after you change the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
1FH
(Determined by protocol)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after
you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
3
(Determined by protocol)
H5-03
(0427)
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload Now] after
you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
0
(0 - 2)
H5-04
(0428)
Communication Error Stop
Method
Sets the motor Stopping Method when the drive detects a Modbus Communication Error condition.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Run at H5-34 (CE Go-To-Freq)
3
(0 - 4)
H5-05
(0429)
Comm Fault Detection
Selection
Sets the function that detects CE [Modbus Communication Error] issues during MEMOBUS/
Modbus communications.
0 : Disabled
1 : Enabled
1
(0, 1)
H5-06
(042A)
Drive Transmit Wait Time Sets the time to wait to send a response message after the drive receives a command message from
the master.
Note:
Restart the drive after changing the parameter setting.
5 ms
(0 - 65 ms)
H5-08
(062D)
Communication Protocol
Selection
Selects the communication protocol.
0 : Modbus/MEMOBUS
1 : Metasys/N2
2 : Apogee/P1
3 : BACnet
3
(0 - 3)