Parameter List
7
7.8 H: Terminal Functions
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 209
No.
(Hex.)
Name Description
Default
(Range)
H5-09
(0435)
CE Detection Time Sets the detection time for CE [Modbus Communication Error] issues when communication stops. 2.0 s
(0.0 - 10.0 s)
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H
(output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
0
(0, 1)
H5-11
(043C)
Comm ENTER Command
Mode
Sets the function to make the Enter command necessary to change parameters through MEMOBUS/
Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
0
(0, 1)
H5-14
(310D)
BACnet Device Obj ID
LOW BITS
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number. 0001
(0000 - FFFF)
H5-15
(310E)
BACnet Device Obj ID
HIGH BITS
Sets the upper bits of the BACnet device object ID as a 4-digit hexadecimal number. 0000
(0000 - 003F)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
0 ms
(0 - 100 ms)
H5-20
(0B57)
Communication Parameters
Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
0
(0, 1)
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH).
0 : Disabled
1 : Enabled
0
(0, 1)
H5-23
(158D)
BACnet Max Master Sets the maximum number of master MAC ID to scan to when the drive polls for the next node (Poll
for Master).
7F
(1 - 7F)
H5-24
(3DA0)
BACnet Max Info Frames Sets the maximum number of information frames for BACnet. 3
(1 - 255)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0045H (U1-06)
(0000H - FFFFH)
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0042H (U1-03)
(0000H - FFFFH)
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
0049H (U1-10)
(0000H - FFFFH)
H5-33
(3FB3)
Power-up CALL Alarm Enables and disables CALL [Serial Comm Transmission Error] alarm detection.
0 : Disabled
1 : Enabled
1
(0, 1)
H5-34
(3FB4)
RUN
Comm Error (CE) Go-To-
Frequency
Sets the speed at which the drive will run when H5-04 = 4 [Communication Error Stop Method =
Run at H5-34] and there is a CE.
0.0 Hz
(0.0 - 400.0 Hz)
H5-35
(3FB5)
RUN
Comm Error (CE) Go-To-
Timeout
When H5-04 = 4 [Communication Error Stop Method = Run at H5-34] and a CE is present, the drive
will run at the H5-34 [Comm Error (CE) Go-To-Frequency] speed for this length of time before it
triggers a CE fault.
Note:
Set this parameter to 0 s to disable the time-out.
0 s
(0 - 6000 s)
H5-36
(3FB6)
CE Fault Restart Select Sets the drive to restart (L5-01 [Number of Auto-Restart Attempts]) after a CE fault.
0 : No Retry
1 : Retry
0
(0, 1)