Parameter List
7
7.15 Z: Bypass Parameters
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 249
â—† Z3: Bypass Control Serial Comm
No.
(Hex.)
Name Description
Default
(Range)
Z3-12
(850B)
Network Digital Inputs Enables and disables control of the digital inputs over a network. It is not necessary to wire to the
physical digital input.
0 : Disabled
1 : Enabled
0
(0, 1)
Z3-13
(850C)
BACnet Register Retention Sets what to restore when you lose power then reapply power.
WARNING! Sudden Movement Hazard. Clear all personnel from the
drive, motor, and machine area before you reapply power. If you set this
parameter to 2 or 3, the bypass unit can start before it receives a valid
network message. Failure to obey can cause injury to personnel.
0 : Disabled
1 : Restore Frequency Reference Only
2 : Restore Commands Only
3 : Restore Commands and Freq Ref
0
(0 - 3)
Z3-16
(850F)
Apogee Run Enable LDO35 This parameter is applicable only when H5-08 = 2 [Communication Protocol Selection = Apogee/
P1].
Sets whether the data in point LDO 35 will have an effect on the ability of the bypass to run.
0 : Disabled
1 : Enabled
0
(0, 1)