EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.15 Z: Bypass Parameters
248 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Setting Value Function Description
8 Drive RUN active The digital output activates when the system is in Drive Mode and the HV600 drive is running.
ON : Running in Drive Mode
OFF : Not running or in Bypass Mode
9 Bypass RUN active The digital output activates when the system is in Bypass Mode and is running. Contactor K3 is closed.
ON : Running in Bypass Mode
OFF : Not running or in Drive Mode
10 HAND mode Active The digital output activates when the system is running in HAND Mode during Drive Mode and Bypass Mode.
ON : Running in HAND Mode
OFF : Not running or in AUTO Mode
11 OFF mode Active The digital output activates when the HAND/OFF/AUTO selection is in OFF Mode or if system is faulted. It is also active when in
Emergency Override Mode.
ON : System is in OFF Mode or is faulted
OFF : HAND Mode, AUTO Mode (even if not running), Emergency Override.
12 Auto mode Active The digital output activates when the HAND/OFF/AUTO selection is in AUTO Mode. It will activate when the system is running
and when the system is not running and in Drive Mode and Bypass Mode.
ON : System is in AUTO Mode
OFF : HAND Mode, OFF Mode, Faulted, Emergency Override
13 Drive Mode Selected The digital output activates when Drive Mode is selected. It stays active during Remote Transfer to Bypass, Emergency Override
Bypass, Energy Savings, Fault condition, and when the system is not running.
ON : Drive Mode is selected
OFF : Bypass Mode is selected
14 Bypass Mode Selected The digital output activates when Bypass Mode is selected. It stays active during Emergency Override Drive, Fault condition, and
when the system is not running.
ON : Bypass Mode is selected
OFF : Drive Mode is selected
15 Fault Active Set when there is an active Drive fault or Bypass fault.
16 Drive Fault Active There is a fault in the HV600 drive.
17 Bypass Fault Active There is a fault in the bypass.
18 Auto Transfer Active There is a drive fault that activated Auto Transfer to Bypass.
19 Serial Run Active Serial Communications is commanding a RUN.
20 Damper Actuator Output System commanded to RUN in Drive Mode or Bypass Mode.
21 ON Always This digital output is always active.
22 Loss of Load Detected The motor current is less than the set value/values.
23 Run Verify Active The digital output closes when the drive or bypass output current is more than 10% of E2-01.
The digital output opens when the drive or bypass output current is less than 5% of E2-01.
24 Soft Starter Run Command Controls the soft starter Run command to ramp down the soft starter before it opens bypass contactor K3.
25 Safeties Closed All of the programmed safety digital inputs are satisfied.
26 Mirror HV600 M1-M2 The digital output activates when the HV600 drive digital output (M1-M2) is closed.
ON : Digital Output M1-M2 on HV600 is closed
OFF : Digital Output M1-M2 on HV600 is open
27 Mirror HV600 M3-M4 The digital output activates when the HV600 drive digital output (M3-M4) is closed.
ON : Digital Output M3-M4 on HV600 is closed
OFF : Digital Output M3-M4 on HV600 is open
28 Mirror HV600 M5-M6 The digital output activates when the HV600 drive digital output (M5-M6) is closed.
ON : Digital Output M5-M6 on HV600 is closed
OFF : Digital Output M5-M6 on HV600 is open
99 Not Used This setting allows serial communications to control the output.

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals