8.3 BACnet Communications
276 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AV4
Drive Multi-Function
Output Command
(MF Output Cmd)
• bit 0: Multi-Function
Digital Output 1
(terminal M1-M2)
• bit 1: Multi-Function
Digital Output 2
(terminal M3-M4)
• bit 2: Multi-Function
Digital Output 3
(terminal M5-M6)
• bit 3: Reserved
• bit 4: Reserved
• bit 5: Reserved
• bit 6: Enables the
function in bit 7
• bit 7: Fault Contact
Output (terminal
MA-MB-MC)
• bit 8 to F: Reserved
Note:
When using AV4, do
not use BO1 to BO3
or BV12.
0009h - 0-255 Bitmap C
AV5
Drive Reference Select
Command
(Reference Select Cmd)
• bit 0: Reserved
• bit 1: PID Setpoint
Input
• bit 2: Reserved
• bit 3: Reserved
• bit 4: PI2 Target
Input
• bit 5 to B: Reserved
• bit C: Multi-Function
Input 5
• bit D: Multi-Function
Input 6
• bit E: Multi-Function
Input 7
• bit F: Reserved
Note:
When you use AV5,
you must not use
AV1, BO4, or BV9
to BV11.
000Fh - 0-32767 Bitmap C
AV6
System Status
(Drive Status)
• bit 0: During Run
(drive or bypass)
• bit 1: During Reverse
• bit 2: System ready
• bit 3: System faulted
• bit 4: Data Setting
Error
• bit 5: Multi-Function
Digital Output 1
(terminal M1-M2)
• bit 6: Multi-Function
Digital Output 2
(terminal M3-M4)
• bit 7: Multi-Function
Digital Output 3
(terminal M5-M6)
• bit 8 to D: Reserved
• bit E: ComRef status
• bit F: ComCtrl status
0020h - 0-65535 Bitmap R