Network Communications
8
8.3 BACnet Communications
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup 275
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AI8 Inverter Model o2-04 0508h XXXXX 0-65535 - R
AI9 Rated Current n9-01 05D0h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A R
AI10 Motor Current UB-01 8780h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A R
AI11 Contactor Voltage 8790h XXXXX 0-65535 V R
â–  Analog Output Objects
Object ID
Object Name
(Network Display)
Modbus Reg. Precision Range Units PV Access
AO1
Drive Terminal FM
Analog Output Level
Command (set H4-01 =
0)
(Drv Anlg Out1 Level)
0007h XXX.X 0-100.0 % C
AO2
Drive Terminal AM
Analog Output Level
Command (Set H4-04 =
0)
(Drv Anlg Out2 Level)
0008h XXX.X 0-100.0 % C
â–  Analog Value Objects
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AV1
Drive Operation
Command
(Operation Cmd)
Note:
Do not command
bypass using AV1.
Use BV58 to BV71
instead.
0001h - 0-65535 Bitmap C
AV2 Frequency Cmd 0002h
XXX.XX
Determined by o1-03
0-600.00 Determined by o1-03 C
AV3 PI Setpoint Cmd 0006h XXX.XX 0-100.00 % C