8.3 BACnet Communications
274 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Property
Object Type
Device
Analog
Input
(AI)
Analog
Output
(AO)
Analog
Value
(AV)
Binary
Input
(BI)
Binary
Output
(BO)
Binary
Value
(BV)
Segmentation_Supported Yes - - - - - -
Local_Time Yes - - - - - -
Local_Date Yes - - - - - -
ADPU_Timeout Yes - - - - - -
Number_Of_ADPU_Retries Yes - - - - - -
Max_Masters Yes - - - - - -
Max_Info_Frames Yes - - - - - -
Device_Address_Binding Yes - - - - - -
Database_Revision Yes - - - - - -
Active_COV_Subscriptions Yes - - - - - -
Present_Value - Yes Yes Yes Yes Yes Yes
Status_Flags - Yes Yes Yes Yes Yes Yes
Event_State - - - - - - -
Reliability - Yes Yes Yes Yes Yes Yes
Out_Of_Service - Yes Yes Yes Yes Yes Yes
Units - Yes Yes Yes - - -
Priority_Array - - Yes
*1
Yes
*1
- Yes Yes
Relinquish_Default - - Yes
*1
Yes
*1
- Yes Yes
Polarity - - - - Yes Yes -
Inactive_Text - - - - Yes Yes Yes
Active_Text - - - - Yes Yes Yes
COV_Increment
*2
- Yes Yes Yes - - -
Property_List Yes Yes Yes Yes Yes Yes Yes
Local Time Yes - - - - - -
Local Date Yes - - - - - -
*1 For Commandable Object Instances only.
*2 COV function is only available on objects that are not commandable and not writable.
â– Analog Input Objects
Object ID
Object Name
(Network Display, if
Different)
Modbus Reg. Precision Range Units PV Access
AI1
Drive Analog Input 1
Level
(Drv Anlg In 1 Level)
004Eh XXX.X 0-100.0 % R
AI2
Drive Analog Input 2
Level
(Drv Anlg In 2 Level)
004Fh XXX.X 0-100.0 % R
AI3 Not Used AI3 - - - % R
AI4
Bypass Analog Input 1
Level
(Byp Anlg In 1 Level)
8795h XXX.X 0-100.0 % R
AI5 Not Used AI5 - - - - R
AI6 Display Format o1-03 0502h XXXXX 0-65535 - R
AI7 Scale Format b5-20 01E2h XXXXX 0-65535 - R