User Constant Tables
5-31
* The factory setting will change when the control method is changed. The flux vector factory setting is given.
Field Weakening: d6
User constants for the field weakening command are shown in the following table.
d5-06
Speed/torque
control
switching
timer
Set the delay time from input-
ting the multi-function input
“speed/torque control
change” (from On to OFF or
OFF to ON) until the control
is actually changed, in ms
units.
This function is enabled when
the multi-function input
“speed/torque control
change” is set. In the speed/
torque control switching
timer, the analog inputs hold
the values of when the
“speed/torque control
change” changes. Always be
sure to allow time for this
process to finish completely.
0 to
1000
0 No No No No A A 29FH 6-128
控制切换时间
d5-07
Rotation
direction
limit
operation
selection
0: Disabled
1: Enabled
Usually, use a setting of 1
(enabled).
Be sure to enable this setting
when rotating the motor in
the same direction as the
speed limit (winding opera-
tion).
0 or 1 1 No No No No No A 2A6H 6-128
旋转方向限制
动作
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d6-01
Field weak-
ening level
Set the Inverter output volt-
age when the field weakening
command is input.
It is enabled when the field
weakening command is set
for a multi-function input.
Set the level as a percentage
taking the voltage set in the
V/f pattern as 100%.
0 to
100
80% No A A No No No 2A0H -
弱励磁值
d6-02
Field
frequency
Set the lower limit in hertz of
the frequency range where
field control is valid.
The field weakening com-
mand is valid only at frequen-
cies above this setting and
only when the speed is in
agreement with the current
speed reference.
0.0 to
400.0
0.0 Hz No A A No No No 2A1H -
励磁频率
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA varispeed G7 CIMR-G7B series and is the answer not in the manual?

YASKAWA varispeed G7 CIMR-G7B series Specifications

General IconGeneral
BrandYASKAWA
Modelvarispeed G7 CIMR-G7B series
CategoryInverter
LanguageEnglish

Related product manuals