5-32
d6-03
Field forcing
function
selection
Set the field forcing function.
0: Disabled
1: Enabled
0 or 1 0 No No No A A A 2A2H -
励磁增强功能
d6-05
AφR time
constant
Set the factor to multiple
times the secondary circuit
time constant of the motor to
achieve the AφR time
constant.
AφR time constant =
Secondary circuit time
constant x d6-05
AφR will not function when
d6-05 is 0. If d6-05 is not 0,
the lower limit of the value
will be internally adjusted to
200 ms in the Inverter.
0.00 to
10.00
1.00 No No No No No A 2A4H -
励磁控制时间
参数
d6-06
Field forcing
limit
Set the excitation current ref-
erence’s upper limit for field
forcing. Set the limit as a per-
centage, taking the motors
no-load current as 100%.
Enabled for operation other
than DC excitation.
Usually, there is no need to
change this setting.
100 to
400
400% No No No A A A 2A5H -
励磁增强极限
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2