User Constant Tables
5-49
Multi-function Contact Output Functions
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 During run (ON: Run Command is ON or voltage is being output) Yes Yes Yes Yes Yes 6-86
1 Zero-speed Yes Yes Yes Yes Yes 6-86
2 Frequency agree 1 (L4-02 used.) Yes Yes Yes Yes Yes 6-51
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and dur-
ing frequency agree)
Yes Yes Yes Yes Yes 6 -5 1
4
Frequency (FOUT) detection 1 (ON: +L4-01 output frequency -L4-01, L4-02
used)
Yes Yes Yes Yes Yes 6 -5 1
5
Frequency (FOUT) detection 2 (ON: Output frequency +L4-01 or output fre-
quency -L4-01, L4-02 used)
Yes Yes Yes Yes Yes 6 -5 1
6
Inverter operation ready
READY: After initialization, no faults
Yes Yes Yes Yes Yes -
7 During DC bus undervoltage (UV) detection Yes Yes Yes Yes Yes -
8 During baseblock (ON: during baseblock) Yes Yes Yes Yes Yes -
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes Yes Yes -
A Run Command selection status (ON: Run Command from Operator) Yes Yes Yes Yes Yes -
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque
detection at ON)
Yes Yes Yes Yes Yes 6 -5 4
C Loss of frequency reference (Effective when 1 i s s e t fo r L4-05) Yes Yes Yes Yes Yes 6 - 7 1
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes Yes 6-74
E
Fault (ON: Digital Operator communications error or fault other than CPF00 and
CPF01 has occurred.)
Yes Yes Yes Yes Yes -
F Not used. (Set when the terminals are not used.) - - - - - -
10 Minor fault (ON: Alarm displayed) Yes Yes Yes Yes Yes -
11 Fault reset command active Yes Yes Yes Yes Yes -
12 Timer function output Yes Yes Yes Yes Yes 6-105
13 Frequency agree 2 (L4-04 used) Yes Yes Yes Yes Yes 6-51
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and dur-
ing frequency agree)
Yes Yes Yes Yes Yes 6 -5 1
15 Frequency detection 3 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-51
16 Frequency detection 4 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes Yes Yes 6-51
17 Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-54
18 Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON) Yes Yes Yes Yes Yes 6-54
19 Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes 6-54
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes Yes -
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes Yes -
1C Motor selection (Motor 2 selected) Yes Yes Yes Yes Yes -
1D During regeneration (ON: During regeneration) No No No Yes Yes -
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes Yes 6-72
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detec-
tion level)
Yes Yes Yes Yes Yes
6-58
6-87
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes Yes 6-87