EasyManua.ls Logo

YASKAWA varispeed G7 CIMR-G7B series - Multi-function Analog Inputs: H3

YASKAWA varispeed G7 CIMR-G7B series
495 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-50
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
2F
Maintenance Time
ON: The operation time of either the electrolytic capacitors or the cooling fan has
reached the specified maintenance time.
Yes Ye s Yes Yes Yes -
30 During torque limit (current limit) (ON: During torque limit) No No Yes Yes Yes -
31 During speed limit (ON: During speed limit) No No No Yes No 6-87
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected (internal
torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
No No No Yes Yes
6-129
33 Zero-servo end (ON: Zero-servo function completed) No No No Yes No
6-87
6-146
36
Frequency (FOUT) detection 5 (ON: Output frequency + L4-01 or output
frequency L4-01, L4-02 used, OFF: during baseblock
Yes Ye s Yes Yes Yes 6 - 5 0
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, ini-
tial excitation, operation stop)
Yes Ye s Yes Yes Yes 6 - 8 6
3D
Inverter's Cooling Fan Fault detected Yes Yes Yes Yes Yes 6-73
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H3-01
Signal level
selection (ter-
minal A1)
0: 0 to 10 V
1: -10V to 10 V
[11-bit + polarity (posi-
tive/negative) input]
0 or 1 0 No A A A A A 410H 6-28
端子 A1 信号
选择
H3-02
Gain (termi-
nal A1)
Sets the frequency when 10 V
is input, as a percentage of the
maximum output frequency.
0.0 to
1000.0
100.0% Yes A A A A A 411H 6-28
端子 A1 增益
H3-03
Bias (termi-
nal A1)
Sets the frequency when 0 V
is input, as a percentage of the
maximum frequency.
-100.0
to
+100.0
0.0% Yes A A A A A 412H 6-28
端子 A1 偏置
H3-04
Signal level
selection (ter-
minal A3)
0: 0 to 10 V
1: -10 V to 10 V
[11-bit + polarity (posi-
tive/negative) input]
0 or 1 0 No A A A A A 413H
6-28
6-128
端子 A3 信号
电平
H3-05
Multi-func-
tion analog
input (termi-
nal A3) func-
tion selection
Select multi-function analog
input function for terminal
A3. Refer to the next page.
0 to 1F 2 No A A A A A 414H
6-28
6-128
端子 A3 设定
H3-06
Gain (termi-
nal A3)
Sets the input gain (level)
when 10 V is input.
Set according to the 100%
value selected from H3-05.
0.0 to
1000.0
100.0% Yes A A A A A 415H
6-28
6-128
端子 A3 增益
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2

Table of Contents