Parameters 115
Fault if running If running, the drive trips on fault 80B0 Signal supervision 1.3
32.07 Supervision 1
signal
Selects the signal to be monitored by signal supervision
function 1.
Frequency
Zero None. 0
Speed 01.01 Motor speed used (page 67). 1
Frequency 01.06 Output frequency (page 67). 3
Current 01.07 Motor current (page 67). 4
Torque 01.10 Motor torque (page 67). 6
DC voltage 01.11 DC voltage (page 67). 7
Output power 01.14 Output power (page 68). 8
AI1 12.11 AI1 actual value (page 84). 9
AI2 12.21 AI2 actual value (page 86). 10
Freq ref used 28.02 Frequency ref ramp output (page 101). 22
Inverter
temperature
05.11 Inverter temperature (page 72). 23
Process PID output 40.01 Process PID output actual (page 130). 24
Process PID
feedback
40.02 Process PID feedback actual (page 130). 25
Process PID
setpoint
40.03
Process PID setpoint actual (page 130). 26
Process PID
deviation
40.04 Process PID deviation actual (page 130). 27
Other Source selection (see Terms and abbreviations on page 64). -
32.08 Supervision 1 filter
time
Defines a filter time constant for the signal monitored by
signal supervision 1.
0.000 s
0.000 30.000 s Signal filter time. 1000 = 1 s
32.09 Supervision 1 low Defines the lower limit for signal supervision 1. 0.00
-21474836.00…
21474836.00
Low limit. -
32.10 Supervision 1 high Defines the upper limit for signal supervision 1. 0.00
-21474836.00…
21474836.00
Upper limit. -
32.11 Supervision 1
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 1.
0.00
0.00…100000.00 Hysteresis. -
32.15 Supervision 2
function
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter 32.17) is compared
to its lower and upper limits (32.19 and 32.20 respectively).
The action to be taken when the condition is fulfilled is
selected by 32.16.
Disabled
Disabled Signal supervision 2 not in use. 0
Low Action is taken whenever the signal falls below its lower limit. 1
High Action is taken whenever the signal rises above its upper
limit.
2
Abs low Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
No. Name/Value Description Def/FbEq16