Parameters 135
40.36 Set 1 output min Defines the minimum limit for the process PID controller
output. Using the minimum and maximum limits, it is possible
to restrict the operation range.
0.00
-100.00...100.00 Minimum limit for process PID controller output. 1 = 1
40.37 Set 1 output max Defines the maximum limit for the process PID controller
output. See parameter 40.36 Set 1 output min.
100.00
-100.00...100.00 Maximum limit for process PID controller output. 1 = 1
40.38 Set 1 output freeze
enable
Freezes (or defines a source that can be used to freeze) the
output of the process PID controller, keeping the output at the
value it was before freeze was enabled. This feature can be
used when, for example, a sensor providing process
feedback must to be serviced without stopping the process.
1 = Process PID controller output frozen
See also parameter 40.30 Set 1 setpoint freeze enable.
Not selected
Not selected Process PID controller output not frozen. 0
Selected Process PID controller output frozen. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Supervision 1 Bit 0 of 32.01 Supervision status (see page 114). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 114). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 114). 23
Other [bit] Source selection (see Terms and abbreviations on page 64). -
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 135 Thursday, February 14, 2019 11:33 AM