Parameters 145
Speed The scaling is defined by parameter 99.09 Motor nominal
speed.
4
Frequency The scaling is defined by parameter 99.08 Motor nominal
frequency.
5
50.08 FBA A actual 2 type Not applicable
50.09 FBA A SW
transparent source
Selects the source of the fieldbus status word when
parameter 50.06 FBA A SW sel is set to Transparent mode.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 64). -
50.10 FBA A act1
transparent source
When parameter 50.07 FBA A actual 1 type is set to
Transparent, this parameter selects the source of actual value
1 transmitted to the fieldbus network through fieldbus adapter
A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 64). -
50.11 FBA A act2
transparent source
Not applicable
50.12 FBA A debug mode This parameter enables debug mode. Shows raw
(unmodified) data received from and sent to fieldbus adapter
A in parameters 50.1350.18.
Disable
Disable Debug mode disabled. 0
Fast Debug mode enabled. Cyclical data update is as fast as
possible which increases CPU load on the drive.
1
50.13 FBA A control word Shows raw (unmodified) control word sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
0.0.0.0
0.0.0.0.0...FF.FF.FF
.FF
Control word sent by master to fieldbus adapter A. -
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
0
-2147483648…
2147483647
Raw REF1 sent by master to fieldbus adapter A. 0
50.15 FBA A reference 2 Not applicable.
50.16 FBA A status word Shows raw (unmodified) status word sent by fieldbus adapter
A to the master (PLC) if debugging is enabled by parameter
50.12 FBA A debug mode.
This parameter is read-only.
0.0.0.0
0.0.0.0.0...FF.FF.FF
.FF
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value
1
Shows raw (unmodified) actual value ACT1 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
0
-2147483648…
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
No. Name/Value Description Def/FbEq16