166 Parameters
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
Reset motor data Restore all motor rating ID run results to default values 2
Restore defaults Restores all editable parameter values to default values,
except
• motor data and ID run results
• I/O extension module settings
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
8
Reset all fieldbus
settings
Restores all fieldbus and communication related settings to
default values.
Note: Fieldbus, control panel and PC tool communication are
interrupted during the restore.
32
Clear all Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control macro selection and the parameter defaults
implemented by it
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it
•group 49 Panel port communication parameters.
62
Reset home view Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
512
Reset end user
texts
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts,
PID unit and currency unit.
1024
All to factory
defaults
Restores all drive parameters and settings back to initial
factory values, except
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
34560
96.07 Parameter save
manually
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power.
The new parameter values are saved automatically when
changed from a PC tool or control panel, after the drive is
powered on for more than 60 seconds.
Save the parameters with this parameter
• to store values sent from the fieldbus
• when using external +24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
• to save the parameter value changes when the drive is
powered off within 60 seconds after being powered on.
Done
Done Save completed. 0
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 166 Thursday, February 14, 2019 11:33 AM