Parameters 81
PFC2 Not applicable.
PFC3 Not applicable.
PFC4 Not applicable.
Event word 1 Not applicable.
User load curve Not applicable.
RO/DIO control
word
Maps to corresponding bit in parameter 10.99 RO/DIO control
word. For example, Bit 0 of 10.99 RO/DIO control word
controls RO1, Bit 1 of 10.99 RO/DIO control word controls
RO2, and so on.
Other [bit] Source selection (see Terms and abbreviations on page 64). -
10.25 RO1 ON delay Defines the activation delay for relay output RO1. 0.0 s
t
On
= 10.25 RO1 ON delay
t
Off
= 10.26 RO1 OFF delay
0.0 … 3000.0 s Activation delay for RO1. 10 = 1 s
10.26 RO1 OFF delay Defines the deactivation delay for relay output RO1. See
parameter 10.25 RO1 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for RO1. 10 = 1 s
10.27 RO2 source Selects a drive signal to be connected to relay output RO2.
For the available selections, see parameter 10.24 RO1
source.
Running
10.28 RO2 ON delay Defines the activation delay for relay output RO2. 0.0 s
t
On
= 10.28 RO2 ON delay
t
Off
= 10.29 RO2 OFF delay
0.0 … 3000.0 s Activation delay for RO2. 10 = 1 s
10.29 RO2 OFF delay Defines the deactivation delay for relay output RO2. See
parameter 10.28 RO2 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for RO2. 10 = 1 s
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
ACQ80 FW.book Page 81 Thursday, February 14, 2019 11:33 AM