-1000…1000% Value in percent
4020 ACT2 MINIMUM See parameter 4018 ACT1 MINIMUM. 0%
-1000…1000% See parameter 4018.
4021 ACT2 MAXIMUM See parameter 4019 ACT1 MAXIMUM. 100%
-1000…1000% See parameter 4019.
4022 SLEEP SELECTION Activates the sleep function and selects the source for the activation input. 0 = NOT SEL
NOT SEL No sleep function selected 0
DI1 The function is activated/deactivated through digital input DI1.1 = activation,
0 = deactivation.
The internal sleep criteria set by parameters 4023 PID SLEEP LEVEL and
4025 WAKE-UP DEV are not effective. The sleep start and stop delay
parameters 4024 PID SLEEP DELAY and 4026 WAKE-UP DELAY are
effective.
1
DI2 See selection DI1. 2
DI3 See selection DI1. 3
DI4 See selection DI1. 4
DI5 See selection DI1. 5
INTERNAL Activated and deactivated automatically as defined by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV.
7
DI1(INV) The function is activated/deactivated through inverted digital input DI1.
1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters 4023 PID SLEEP LEVEL and
4025 WAKE-UP DEV are not effective. The sleep start and stop delay
parameters 4024 PID SLEEP DELAY and 4026 WAKE-UP DELAY are
effective.
-1
DI2(INV) See selection DI1(INV). -2
DI3(INV) See selection DI1(INV). -3
DI4(INV) See selection DI1(INV). -4
DI5(INV) See selection DI1(INV). -5
4023 PID SLEEP LEVEL Defines the start limit for the sleep function. If the motor speed is below a set
level (4023) longer than the sleep delay (4024), the drive shifts to the
sleeping mode: The motor is stopped and the control panel shows alarm
message PID SLEEP (code: A2018).
Parameter 4022 SLEEP SELECTION must be set to 7 (INTERNAL).
0.0 Hz
Parameters
Index Name/Selection Description Def
t < 4024
t
t > 4024
t
4023
4026
4025
PID output level
PID process feedback
PID reference
Stop
Start