Parameters 253
30.12 Maximum speed Defines the maximum allowed speed.
Note: This parameter does not affect the speed acceleration
and deceleration ramp times. See parameter 46.01 Speed
scaling.
WARNING! This value must not be lower than 30.11
Minimum speed.
WARNING! In speed control mode only. In frequency
control mode, use frequency limits (30.13 and 30.14).
1500.00 rpm
-30000.00…
30000.00 rpm
Maximum speed. See par.
46.01
30.13 Minimum frequency Defines the minimum allowed frequency.
WARNING! This value must not be higher than 30.14
Maximum frequency.
WARNING! in frequency control mode only.
-50.00 Hz
-500.00…500.00
Hz
Minimum frequency. See par.
46.02
30.14 Maximum
frequency
Defines the maximum allowed frequency.
Note: This parameter does not affect the frequency
acceleration and deceleration ramp times. See parameter
46.02 Frequency scaling.
WARNING! This value must not be lower than 30.13
Minimum frequency.
WARNING! in frequency control mode only.
50.00 Hz
-500.00…500.00
Hz
Maximum frequency. See par.
46.02
30.17 Maximum current Defines the maximum allowed drive current.
The system sets the default value to 90% of the rated
current. If required, you can increase the parameter value
by 10%.
Note: The maximum current range and default value
depends on the drive type.
2.92 A
0.00...3.24 A Maximum drive current. 1 = 1 A