Parameters 297
In1+In2 Sum of sources 1 and 2. 1
In1-In2 Source 2 subtracted from source 1. 2
In1*In2 Source 1 multiplied by source 2. 3
In1/In2 Source 1 divided by source 2. 4
MIN(In1,In2) Smaller of the two sources. 5
MAX(In1,In2) Greater of the two sources. 6
AVE(In1,In2) Average of the two sources. 7
sqrt(In1) Square root of source 1. 8
sqrt(In1-In2) Square root of (source 1 - source 2). 9
sqrt(In1+In2) Square root of (source 1 + source 2). 10
sqrt(In1)+sqrt(In2) Square root of source 1 + square root of source 2. 11
40.11 Set 1 feedback filter
time
Defines the filter time constant for process feedback. 0.000 s
0.000…30.000 s Feedback filter time. 1 = 1 s
40.14 Set 1 setpoint
scaling
Defines, together with parameter 40.15 Set 1 output
scaling, a general scaling factor for the external PID
control chain. The scaling can be utilized when, for
example, the process setpoint is input in Hz, and the
output of the PID controller is used as an rpm value in
speed control. In this case, this parameter might be set to
50, and parameter 40.15 to the nominal motor speed at 50
Hz.
In effect, the output of the PID controller [40.15] when
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.
Note: The scaling is based on the ratio between 40.14
and 40.15. For example, the values 50 and 1500 would
produce the same scaling as 1 and 3.
0.00
-200000.00...
200000.00
Process setpoint base. 1=1
40.15 Set 1 output scaling See parameter 40.14 Set 1 setpoint scaling 0.00
-200000.00...
200000.00
Process PID controller output base. 1=1
40.16 Set 1 setpoint 1
source
Selects the primary source of process PID setpoint. See the
control chain diagram on page 495.
AI1 percent
Not selected None. 0
Internal setpoint Internal setpoint. See parameter 40.19 Set 1 internal setpoint
sel1.
2
AI1 scaled 12.12 AI1 scaled value (see page 189). 3
AI2 scaled 12.22 AI2 scaled value (see page 191). 4
Motor
potentiometer
22.80 Motor potentiometer ref act (output of the motor
potentiometer).
8
Freq in scaled 11.39 Freq in 1 scaled value (see page 187). 10
AI1 percent 12.101 AI1 percent value (see page 192)11
AI2 percent 12.102
AI2 percent value (see page 192)12