356 Parameters
PID PID macro (see page 116 ). 14
Panel PID Panel PID macro (see page 119). 15
PFC PFC macro (see page 125). 16
SPFC SPFC macro (see page 134). 18
Pharma Application Pharma application (see page 143)19
Plastic Extrusion Plastic extrusion (see page 146)20
Torque control Torque control (see page 122)28
Jigar Jigar macro (see page 149)30
96.05 Macro active Shows which control macro is currently selected. See chapter
Control macros (page 101) for more information.
To change the macro, use parameter 96.04 Macro select.
ABB
standard
ABB standard Factory macro (see page 102). For scalar motor control. 1
ABB standard
(vector)
ABB standard (vector) macro (see page 105). For vector
motor control.
17
3-wire 3-wire macro (see page 108)
Motor
potentiometer
Motor potentiometer macro (see page 111). 13
PID PID macro (see page 116 ). 14
Panel PID Panel PID macro (see page 119). 15
PFC PFC macro (see page 125). 16
SPFC SPFC macro (see page 134)18
Pharma Application Pharma application (see page 143)19
Plastic Extrusion Plastic extrusion (see page 146)20
Torque control Torque control (see page 122)28
Jigar Jigar macro (see page 149)30
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
Reset motor data Restore all motor rating ID run results to default values 2
Restore defaults Restores all editable parameter values to default values,
except
motor data and ID run results
I/O extension module settings
end user texts, such as customized warnings and faults,
and the drive name
control panel/PC communication settings
fieldbus adapter settings
control macro selection and the parameter defaults
implemented by it
parameter 95.20 HW options word 1
and the differentiated
defaults implemented by it.
8
Reset all fieldbus
settings
Restores all fieldbus and communication related settings to
default values.
Note: Fieldbus, control panel and PC tool communication are
interrupted during the restore.
32