218 Parameters
33.43 Edge counter 2
source
Selects the signal to be monitored by signal edge counter 2. False
False 0. 0
True 1. 1
RO1 Bit 0 of 10.21 RO status (page 116). 2
Other [bit] Source selection (see Terms and abbreviations on page 92). -
33.44 Edge counter 2
divider
Defines a divisor for signal edge counter 2. Determines how
many signal edges increment the counter by 1.
1
1…4294967295 Divisor for signal edge counter 2. -
33.45 Edge counter 2
warn message
Selects the optional warning message for signal edge counter
2.
Edge counter
2 exceeded
Edge counter 2
exceeded
A889 Edge counter 2. The message text can be edited on the
control panel by choosing Menu – Settings – Edit texts.
3
Counted main
contactor
A884 Main contactor.11
Counted output
relay
A881 Output relay.12
Counted motor
starts
A882 Motor starts.13
Counted power ups A883 Power ups.14
Counted DC
charges
A885 DC charge.15
33.50 Value counter 1
actual
Displays the actual present value of value counter 1.
The value of the source selected by parameter 33.53 Value
counter 1 source is read at one-second intervals and added to
the counter. A divisor can be applied to the count (see 33.54
Value counter 1 divider).
When the counter exceeds the limit set by 33.51 Value
counter 1 warn limit, bit 4 of 33.01 Counter status is set to 1.
The warning specified by 33.55 Value counter 1 warn
message is also given if enabled by 33.52 Value counter 1
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
-2147483008
2147483008
Actual present value of value counter 1. -
33.51 Value counter 1
warn limit
Sets the limit for value counter 1.
With a positive limit, bit 4 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 4 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
0
-2147483008
2147483008
Limit for value counter 1. -