282   Parameters
90.59 Pos counter init 
value int source
Selects the source of the initial position integer value. When 
the source selected by 90.67 Pos counter init cmd source 
activates, the value selected in this parameter is assumed to 
be the position of the load.
Pos counter 
init value int
Zero 0. 0
Pos counter init 
value int
Parameter 90.58 Pos counter init value int.1
Other Source selection (see Terms and abbreviations on page 92). -
90.60 Pos counter error 
and boot action
Selects how the position counter reacts to loss of load 
feedback.
Request re-
initialization
Request re-
initialization
Bit 4 of 90.35 Pos counter status is cleared. Reinitialization of 
position counter is recommended.
0
Continue from 
previous value
Position counting resumes from the previous value over a loss 
of load feedback or control unit reboot. Bit 4 of 90.35 Pos 
counter status is not cleared, but bit 6 is set to indicate that an 
error has occurred.
WARNING! If load feedback is lost when the drive is in 
stopped state or not powered, the counter is not 
updated even if the load moves.
1
90.61 Gear numerator Parameters 90.61 and 90.62 define a gear function between 
the motor and load speeds.
See also section Load and motor feedback (page 43).
1
-2147483648 … 
2147483647
Gear numerator (motor-side). -
90.62 Gear denominator See parameter 90.61 Gear numerator.1
-2147483648 … 
2147483647
Gear denominator (load-side). -
90.63 Feed constant 
numerator
Parameters 90.63 and 90.64 define the feed constant for the 
position calculation:
The feed constant converts rotational motion into translatory 
motion. The feed constant is the distance the load moves 
during one turn of the motor shaft.
The translatory load position is shown by parameter 90.07 
Load position scaled int. Note that the load position is only 
updated after new position input data is received.
1
-2147483648 … 
2147483647
Feed constant numerator. -
90.64 Feed constant 
denominator
See parameter 90.63 Feed constant numerator.1
-2147483648 … 
2147483647
Feed constant denominator. -
No. Name/Value Description Def/FbEq16
90.61 Gear numerator
90.62 Gear denominator
Motor speed
Load speed
=
90.63 Feed constant numerator
90.64 Feed constant denominator