…Profile Parameters / …Common Settings / …Program Control
Recovery
Action Selects the profile restart action when power is restored after a failure or the PV is restored
after a failure and the Recovery Period (Time – see below) has expired.
Continue
The program resumes from the point at which failure occurred and is placed in
Operator Hold mode.
Repeat
The program resumes from the start of the current segment and is placed in
Operator Hold mode.
Reset
The program resumes from the start of the current program and is placed in
Operator Hold mode.
Advance
The program resumes at the point in the program that would have been reached if no power
failure had occurred in Run mode.
Note. If a zero time period is selected the program will always recover with the chosen option.
Time Set the recovery time period used to determine the recovery action.
The time is configurable in HH:MM:SS.