Parameterization
OI/FEX300/FEX500-EN FEX300, FEX500 107
Menu / Parameter Value range Description
Input/Output / Current Output
Iout at Alarm
High Alarm Value, Low Alarm
Value
Select the status of the current output in error
condition.
The output “low” or “high” current is set in the
subsequent menu.
Default setting: "High Alarm Value".
Low Alarm Value 3,5 ... 3,6 mA Select the current for Low Alarm.
Default setting: 3.5 mA
High Alarm Value 21 ... 23 mA Select the current for High Alarm.
Factory setting: 21.8 mA
Iout at EP Alarm
Off, Q=0%, High Alarm, Low
Alarm
Select the status of the current output for an empty
pipe.
• Off:
Error is not output at the current output.
• Q=0%:
The current output assumes the value for "No
flow".
• High Alarm:
The current output assumes the value for "High
Alarm".
• Low Alarm
The current output assumes the value for "Low
Alarm".
Default setting: "Off".
Iout at Flow >103% Off, High Alarm, Low Alarm
Select the status of the current output for overshoot of
the flow range end value.
• Off:
Error is not output at the current output.
• High Alarm:
The current output assumes the value for "High
Alarm".
• Low Alarm
The current output assumes the value for "Low
Alarm".
Default setting: „Off“.
italics = Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.