Parameterization
108 FEX300, FEX500 OI/FEX300/FEX500-EN
Menu / Parameter Value range Description
Input/Output / Current Output (continued)
Iout at TFE Alarm
Off, Q = 0 %, High Alarm, Low
Alarm
Select the status that the current output shall assume
in the case of a partial filling alarm.
• Off:
Error is not output at the current output.
• Q = 0 %:
The current output assumes the value for "No flow
"(4 mA).
• High Alarm:
The current output assumes the value for "High
Alarm".
• Low Alarm
The current output assumes the value for "Low
Alarm".
Default setting: „Off“.
Iout Mode
4 ... 20 mA, 4 - 12 - 20 mA
Select the operating mode for the current output.
• 4 ... 20 mA
- 4 mA = No flow
- 20 mA = Maximum flow
• 4 - 12 - 20 mA
- 4 mA = Maximum reverse flow
- 12 mA = No flow
- 20 mA = Maximum forward flow
italics = Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.