Parameterization
OI/FEX300/FEX500-EN FEX300, FEX500 117
Menu / Parameter Value range Description
Diagnostics / Diagnosis Control / Sensor Measurements
One shot Sensor Mea
Start the measurement. The measured values for the
start moment are acquired.
Coil Current Display only Display the coil current.
Coil Resistor Display only Display the coil resistance.
Coil Voltage Display only Display the coil voltage.
Coil R. Max Alarm 0 ... 1000 Ω
Set the maximum limit value for the coil resistance. In
the case of overshoot an alarm is tripped.
Default setting: 1000 Ω
Coil R. Min Alarm 0 ... 1000 Ω
Set the minimum limit value for the coil resistance. In
the case of undershoot an alarm is tripped.
Default setting: 0 Ω
Signal-Cable length 0.01 ... 200 m
Enter the signal cable length between the transmitter
and the flowmeter sensor. For devices with a compact
design 0.01 m must be entered.
Default setting: 0 m
Sensor Temp Value
1)
Display only Display the sensor temperature.
Adj. Sensor T. Value
1)
-50 ... +200 °C
The sensor temperature must be adjusted according
to the conditions on site. The temperature measured
with a separate thermometer can be entered here.
Sensor T. Max Alarm
1)
-50 ... +200 °C
Set the maximum limit value for the sensor
temperature. In the case of overshoot an alarm is
tripped.
Default setting: -50 °C
Sensor T. Min Alarm
1)
-50 ... +200 °C
Set the minimum limit value for the sensor
temperature. In the case of undershoot an alarm is
tripped.
Default setting: +200 °C
italics = Parameter can only be viewed at the "Advanced" password level.