Commissioning
70 FEX300, FEX500 OI/FEX300/FEX500-EN
Possible parameter settings Factory setting
Digital Input Setup No Function, Totalizer
Reset(All), Flowrate to Zero,
System Zero Adjust, Totalizer
Stop(All), Only available for
FEP500 / FEH500 are:
Dual Range, Start/Stop
Batching
Flowrate to Zero
Current Output 4 … 20 mA, 4 … 12 … 20 mA 4 - 20 mA
Iout at Alarm High Alarm, can be set to
21 … 23 mA or
Low Alarm, can be set to
3.5 … 3.6 mA
High Alarm, 21.8 mA
For details refer to Section
9.2.
Iout at Flow >103% Off (no signaling, current
output holds 20.5 mA), High
Alarm, Low Alarm
Off
Low Flow Cut Off 0 … 10 % 1 %
Empty Pipe Detector On / Off Off
TFE Detector On / Off Off
For PROFIBUS PA version
Possible parameter settings Factory setting
PA Addr. (BUS) 0 … 126 126
ID Nr Selector 0x9700, 0x9740, 0x3430 0x3430