ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-66
D. Peak value current function settings - Current-Inst
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 0000000
0
Delay s 00.01 0.00 60.00 0.01
I-Setting IN 04.00 0.1 20 0.1
f-min Hz 40 2 50 1
MaxMin MAX (Select)
NrOfPhases 001 1 3 2
CurrentInp CT/VT-Addr 0
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping output of
the function (matrix).
Delay
Time between the function picking up and tripping.
I-Setting
Pick-up current setting.
Setting restrictions:
· not > 1.6 I
N
when supplied from metering cores
· not < 0.2 I
N
when supplied from protection cores.
f-min
defines the minimum frequency for which measurement is
required.
Setting restriction:
not < 40 Hz when supplied from metering cores.