REG 316*4 1MRB520049-Uen / Rev. C ABB Switzerland Ltd
7-19
The following example is of a ROM defect in the main processor
unit:
List DiagInfo:
MODURES 316 Diagnosis
Relay status : fatal error
Main processor VC61 status : Fault detected
ROM
HW number : 000000B0A538
Software = 1995-08-11 11:38;00
Setting = 1992-01-03 09:44;05
Protection stop
A/D processor EA6. status : not ready
internal A/D status : no error
FUPLA status: FUPLA not loaded
Press any button to continue; press <ESC> to close.
Get Hex Dump:
1000:0000 0004 Error code = stopped
1000:0002 0000 Code segment = 00D8H
1000:0004 06D9 Module name = RUNPROT_TEXT
1000:0006 00D8 Program counter = 06D9H
1000:0008 0004
1000:000A 0052
1000:000C 01F1
1000:000E 0178 EEPROM: 00000000000000101
1000:0010 0199
1000:0012 00A0
1000:0014 00E1
1000:0016 0730
1000:0018 0000
1000:001A 0000
1000:001C 0000
1000:001E 0005.
7.4.1.3. Restarting
The detection of an error or defect by the self-testing and moni-
toring functions during normal operation initiates the following:
· Processing by the protection functions is stopped and their
operation blocked.
· The binary outputs are reset and further operation blocked.
This includes resetting the ‘Relay ready’ signal, if it was acti-
vated.
· The stand-by signal (green LED on the frontplate) flashes.
Communication between the PC and the protection equipment
remains intact, however, and provides facility for localising the
cause of the problem.
Blocking of the protection is maintained until an attempt is made
to restart it by pressing the reset button on the frontplate. Should
restarting be successful, but the original defect still exists, the
same sequence is repeated and the protection is blocked once
again.