ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-28
5.5.2. Adding a new function
An additional function is added either by selecting the second
last menu item “Insert function” from the “Present prot. funcs.”
menu (see Fig. 5.3 i) or a “No function” line if there is one. Upon
pressing <Enter>, a list of the available functions appears. Select
the desired function from the list and press <Enter> again. This
opens the “Edit function parameters” window (see Fig. 5.3 c) and
the parameters can be set. The procedure for the different kinds
of parameters is explained in Sections 5.5.3. and 5.5.4.
The last entry in the list of available functions is “No function”.
Selecting this line and pressing <Enter> adds a “No function” line
to the list of active functions. This method can be used, for ex-
ample, to adjust the list so that a given function has the same
number in all the relays although.
5.5.3. General information on editing parameters
There are two types of parameters, which have to be entered:
1. those requiring the entry of a numerical value, e.g. current or
voltage settings
2. those requesting selection from a list of alternatives, e.g. op-
tions or channels
Window used for both types of parameters:
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛABB Switzerland LtdÛÛÛÛÛÛÛÛÛÛÛÛExampleÛÛÛÛÛÛÛÛÛÛÛÛÛREG316*4 Generator TerminalÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛÉEdit Function ParametersÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ»Û
Ûº ºÛ
Ûº Func Nr 2 - Voltage-DT * V> Max Voltage * ºÛ
Ûº ºÛ
Ûº ParSet4..1 P1 Select ºÛ
Ûº Trip B10300000 ºÛ
Ûº Delay 02.00 s ºÛ
Ûº V-Setting 1.200 UN ºÛ
Ûº MaxMin MAX (1ph) Select ºÛ
Ûº NrOfPhases 001 ºÛ
Ûº VoltageInp 6 AnalogAddr ºÛ
Ûº BlockInp f 1 Trip BinaryAddr ºÛ
Ûº Trip S104 L03 SC1307 ER SignalAddr ºÛ
Ûº Start S103 ER SignalAddr ºÛ
Ûº RETURN/ENTER ºÛ
Ûº ºÛ
Ûº ºÛ
Ûº ºÛ
ÛÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛOn - Line 9600 bps SCS:SPAÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛV6.2b | V6.2bÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
Fig. 5.4 List of parameters