REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-297
3.6.1.1.2. Timers
EXTIN signals of the time factor type and signals belonging to
the TMSEC group are displayed in this window.
The signals can be connected to the following sources:
· Measured variable constant
Setting range and resolution:
TMSEC signal group: 0...60.000 s, for TON
0...50.00 s, for TONS
TIMEFACTOR signal group: 0...4000 s, for TONL
· Protection function binary output (measured variable)
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
· Input from the IBB
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
3.6.1.1.3. Binary inputs
Binary inputs can be connected to the following sources:
· Always ON (“1”)
· Always OFF (“0”)
· Binary system inputs
· Protection function binary outputs
· Inputs from the IBB: 768 inputs in 24 groups of 32 signals
each.
3.6.1.1.4. Binary signals
Binary signals can be connected to the following sinks:
· LED’s
· Signalling relays
· Event processor (excluding ‘BinExtOut’ blocks)
· Protection function binary inputs
· Tripping channels
· Outputs to the IBB: 768 inputs in 24 groups of 32 signals
each.