3.5.16. Stator overload (OLoad-Stator)
A. Application
Overload protection for the stators of large generators.
B. Features
· delay inversely proportional to overload (see Fig. 3.5.16.1)
· operating characteristic according to ASA-C50.13 (American
Standard Requirements for Cylindrical-Rotor Synchronous
Generators) with extended setting range
· adjustable rate of counting backwards when the overload
disappears (cooling rate of thermal image)
· insensitive to DC components
· insensitive to harmonics
· single or three-phase measurement
· detection of highest phase in the three-phase mode.
C. Inputs and outputs
I. Analogue inputs:
· current
II. Binary inputs:
· blocking
III. Binary outputs:
· pick-up
· tripping
IV. Measurements:
· current amplitude.