REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-123
5.13.9. Automatic display
5.13.9.1. General description
In addition to the manual procedure for selecting information for
display, there is an automatic display routine that cyclically pres-
ents the available information. It runs whenever the PC is not
connected and no buttons on the LDU are being pressed.
5.13.9.2. Automatic display sequence
After the system has been started, the entry menu appears. The
automatic display cycle starts providing no buttons are pressed
for a minute. A particular menu item (e.g. measurements) that
has been selected manually remains on the display even if no
buttons are pressed. The automatic display routine only starts
from the entry menu providing no buttons are pressed and the
PC with the HMI is not connected.
5.13.9.3. Stopping the automatic display routine
Stop the automatic display routine by pressing the button “C”
(clear button). The entry menu appears and you can navigate
through the menu structure in the normal way.
5.13.9.4. Automatic display cycle
The sequence of the automatic display cycle is as follows:
· Entry menu
· Measurement(s) of 1st. function
· Measurement(s) of 2nd. function
· ....
· Measurement(s) of last function
· Event list.
In each case, the information remains visible for about 15 sec-
onds before switching to the next block of information. Where a
function generates more than three measurements, all of them
are shown in sequence before the display proceeds to the next
function. The same applies when there are more than three
events in the event list.