REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-39
Bottom: u (used) : channel in use
X : selected channel.
The ITL assignment (e.g. I101) is indicated in the parameter
value column of the “Edit function parameters” window.
Iyxx: y = ITL group number (1...3)
xx = data node within a group (1...16).
5.5.4.3. Tripping channels
The tripping signals of the various functions can be assigned to
one or several tripping channels in order to achieve the required
tripping logic:
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛABB Switzerland LtdÛÛÛÛÛÛÛÛÛÛÛÛExampleÛÛÛÛÛÛÛÛÛÛÛÛÛREG316*4 Generator TerminalÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛÚEdit Function ParametersÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ¿Û
Û³ ³Û
Û³ Func Nr 2 - Voltage-DT * V> Max Voltage * ³Û
Û³ ³Û
Û³ ParSet4..1 P1 Select ³Û
Û³ Trip B10300000 ³Û
Û³ Delay 02.00 s ³Û
Û³ V-Setting 1.200 UN ³Û
Û³ MaxMin MAX (1ph) Select ³Û
Û³ NrOfPhases 001 ÉTrip Output ChannelsÍÍÍÍÍ» ³Û
Û³ VoltageInp 6 º º ³Û
Û³ BlockInp f 1 Trip ºÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄ¿º ³Û
Û³ Trip S104 L03 SC1307 ERº³ 1³ 2³ 3³ 4³ 5³ 6³ 7³ 8³º ³Û
Û³ Start S103 ER º³X ³ ³X ³ ³- ³- ³- ³- ³º ³Û
Û³ RETURN/ENTER ºÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÙº ³Û
Û³ º º ³Û
Û³ º º ³Û
Û³ ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ ³Û
ÛÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛOn-line 9600 bps SCS:SPAÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛV6.2b | V6.2bÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
Fig. 5.15 “Trip output channel” selection window
The fields representing the tripping channels in the selection
window are designated as follows:
Top: 1...8 : Channel No.
Bottom: - : Non-existent tripping channel
X : selected channel.
Any user comment is displayed in the lower part of the window
for the channel currently selected.
Only I/O units types 316DB61 and 316DB62 are equipped with
two tripping relays.