ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-54
· Primary/secondary ratio:
These values are only of consequence in connection with the
VDEW6 protocol. The ratio of all three channels of a three-
phase group change when one is changed.
· Change reference value:
Reference values enable the protection ratings to be adjusted
to those of the primary plant. The reference values of all three
channels of a three-phase group change when one is changed.
5.5.5.3. Excluding (masking) binary channels as events
Binary channels can be excluded from counting as events and
appearing in the event list.
Upon selecting the menu item “Edit enable / event mask”, the
window opens for changing the corresponding settings. The
channels are displayed in groups of eight and each one can be
selected and the mask set by pressing <Ins> or removed by
pressing <Del>.
The channels appear in the parameter value column of the “Edit
function parameters” window as a bit string with ‘1’ to ‘8’ indicat-
ing the masked channels and ‘0’ the non-masked channels (e.g.
12300670). The parameters that start with “R” concern the dis-
tributed input system.
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛABB Switzerland LtdÛÛÛÛÛÛÛÛÛÛÛÛExampleÛÛÛÛÛÛÛÛÛÛÛÛÛREG316*4 Generator TerminalÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛÚEdit Function ParametersÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ¿Û
Û³ ³Û
Û³ BinInp Card * * ³Û
Û³ ³Û
Û³ 01 / 01-08 B12300670 ³Û
Û³ 01 / 09-16 B00000000 ³Û
Û³ 02 / 01-08 B00000000 ³Û
Û³ 02 / 09-16 B00000000 ³Û
Û³ 03 / 01-08 B00000000 ³Û
Û³ 03 / 09-16 B00000000 ÉÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍ» ³Û
Û³ 04 / 01-08 B00000000 º º ³Û
Û³ 04 / 09-16 B00000000 ºÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄ¿º ³Û
Û³ R01 / 01-08 B00000000 º³ 1³ 2³ 3³ 4³ 5³ 6³ 7³ 8³º ³Û
Û³ R01 / 09-16 B00000000 º³X ³X ³X ³ ³ ³X ³X ³ ³º ³Û
Û³ R02 / 01-08 B00000000 ºÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÙº ³Û
Û³ R02 / 09-16 B00000000 ºCB open º ³Û
Û³ R03 / 01-08 B00000000 º º ³Û
Û³more... ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ ³Û
ÛÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛOn - Line 9600 bps SCS:SPAÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛV6.2b | V6.2bÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
Fig. 5.27 Changing the event masking settings