ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-24
Rem. Setting (see Section 5.11.1.):
Input for switching between sets of parameters.
F: - Sets of parameters can only be switched by ap-
plying signals to the binary inputs “ParSet 2-4".
T: - Sets of parameters can only be switched by signals
from the station control system.
xx: - all binary inputs
ParSet2...ParSet 4 (see Section 5.11.1.):
Individual inputs for activating the different sets of
parameters.
ParSet1...ParSet 4 (see Section 5.11.1.):
Signal indicating that one of the sets of parameters 1-4 is ac-
tive.
Modem Error:
Signal indicating a data transmission error on the optical link
between two longitudinal differential relays. This signal is
generated instantly in the event of an error (see Section 3.8.
Data transmission from REL 316*4).
The diagnostic function reports this error after a delay of
80 ms, i.e. only when it is certain that the communications
channel is permanently disturbed.
QuitStatus:
Signals that the reset button on the front of the unit has been
operated.
MVB_PB_Warn, MVB_PB_Crash,
PB_BA1Ready…PB_BA4Ready, PB LA faulty, PB LB faulty
These messages are only generated when using an MVB
process bus (see Operating Instructions for the remote I/O
system RIO580, 1MRB520192-Uen).
3.4.5.2. Edit system name
A name can be entered which then appears on the first line of
the HMI displays.
3.4.5.3. Edit system password
This enables an existing password to be replaced by a new one.