5.11.2.2. Copying a protection function with its settings
A protection function can be copied together with its settings
from one set of parameters to another, if its settings in the sec-
ond set of parameters remain mostly the same. The procedure is
described in Section 5.5.1.3.
The copied Version of the protection function assumes precisely
the same settings as the original function. The following parame-
ters of a copied function cannot be changed subsequently
· all analogue inputs
· all signalling outputs
· all tripping channels.
The copied function must not be active in the same set of pa-
rameters as the original and the parameter set number of the
original function must be lower:
RULE: P1 £ pO £ P4 <---> pO < pK £ P4
pO = parameter set number of the original function
pK = parameter set number of the copied function.
The originals of existing copied functions cannot be deleted.