REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-89
The modem must be set to answer automatically when it re-
ceives a call.
Initialisation string for the remote modem:
Fixed DTE rate: &B1
DTE async speed: 9600 Baud
DTR ignored: &D0
RTS ignored &R1
DSR always on &S0
Auto answer: S0=2
Handshake off: &H0
Save modem settings: AT&W0.
5.12.3. Remote HMI shell
The HMI shell requires an operating system Windows 3.xx, Win-
dows 95 or Windows NT 4.x. Menus guide the user through the
procedures for configuring stations and devices. The device HMI
is started in a DOS window.
5.12.3.1. Installation
Place installation disc No. 1 in drive A and select ‘Run’ in the
‘File’ menu to start the installation.
Fig. 5.61 Starting the installation of the HMI
5.12.3.2. Configuring a new station
After starting the remote HMI, select ‘New station’ in the ‘File’
menu to open the dialogue for entering the station name.