ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-296
3.6.1.1.1. General
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
RepetitRate low low high 1
Cycl. time ho ms 20 0 1000 1
Blocking BinaryAddr F
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
RepetitRate
Determines the number of FUPLA runs per cycle.
high: four FUPLA runs per cycle
medium: two FUPLA runs per cycle
low: one FUPLA run per cycle.
Cycl. time
Determines the interval between FUPLA starts.
Blocking
(F
® FALSE, T ® TRUE, system binary input,
protection function binary output or input via the IBB).
This blocks FUPLA.