EasyManua.ls Logo

ABB REG316 4 Series - Measuring the Voltage Values

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. B
4-18
· Solder in a capacitor or combination of capacitors with the
total value determined for C
X
.
Theoretical value of C
X
a) Circuit according to Fig. 4.8a (or Fig. 4.5):
C
CC C
CC C
X
KK R
KK R
=
++
()
12
12
b) Circuit according to Fig. 4.8b:
C
CCC
CCC
X
K
S
R
K
S
R
=
´+
++
33
33
()
4.2.3.5.3. Measuring the voltage values
The value of the voltage across the bridge as measured on the
YWX 111 in relation to different leakage resistances is deter-
mined by measurement with a variable resistor inserted in place
of the leakage resistance as shown in Fig. 4.6.
Fig. 4.6 Measuring the voltages corresponding to leakage
resistance
Leakage resistor R
P
:
· 0 W, solid ground fault
· 2000 W, ³ 2.5 W
· 5000 W, ³ 2.5 W.

Table of Contents