REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-13
3.4. System parameter settings
3.4.1. Configuring the hardware
Summary of parameters:
Text Unit Default Min. Max. Step
NomFreq Hz 50 50 60 10
A/D on VC61 (Select)
AD Config K 00 00 99 1
Slot Nr 1 Not used (Select)
Slot Nr 2 Not used (Select)
Slot Nr 3 Not used (Select)
Slot Nr 4 Not used (Select)
SWVers SX... X (Select)
SWVers S.XXX 100 1 999 1
Significance of the parameters:
NomFreq
Power system frequency setting:
· 50Hz or 60Hz.
A/D
defines the type of A/D converter. Choose either “EA62…” or
“EA63…” to correspond to the A/D converter unit inserted in
the longitudinal line differential protection:
· on VC61: A/D converter on 316VC61
· EA6. MasterS: short data transmission distance
· EA6. SlaveS: short data transmission distance
· EA6. MasterL: long data transmission distance
· EA6. SlaveL: long data transmission distance
· EA6. MstFoxS: short data trans. distance using FOX
· EA6. MstFoxL: long data trans. distance using FOX
· EA6. SlvFoxS: short data trans. distance using FOX
· EA6. SlvFoxL: long data trans. distance using FOX.
The setting of the data transmission distance is normally
determined by the attenuation of the optical fibre cable (OFC)
between the two units.