EasyManua.ls Logo

ABB REG316 4 Series - Main Menu and Sub-Menus

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-13
5.4. Main menu and sub-menus
The main menu gives the user the choice of performing one of
the following operations:
1. Editor loads the editor and enables all the
protection and system functions to
be listed, changed and saved.
2. Event handling lists all the events in the event
memory and enables the events to
be deleted.
3. Measurements displays protection variables in-
cluding the A/D converter inputs.
4. Test functions checks the protection functions in
the various sets of parameters and
the operation of the LED signals,
tripping relays and signalling re-
lays.
5. Diagnostics provides fault-finding information
for the protection system.
6. SMS010 editor enables events and measured
variables to be configured for proc-
essing by SMS010.
7. Documentation the device configuration can be can
be exported as a text file for use
when engineering the SCS.
8. RETURN closes the operator program.
All the above options are available when the PC is connected
on-line, but only 1, 6, 7 and 8 when it is off-line.
Note:
With the exception of the editor, all the menu items are only rele-
vant when the PC is connected on-line to the protection equip-
ment, e.g. for transferring data. All printed and displayed data
are identical to those loaded in the protection and not related to
those being processed using the editor.

Table of Contents