ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-32
5.5.4. Explanation of the types of channels
There are four types of channels which conform generally to the
rules given in the preceding sections. Each one, however, has in
addition characteristics and abbreviations peculiar to itself.
5.5.4.1. C.t./v.t. input channels
The c.t. and v.t. input channels are assigned in the “A-D Input
Channels” selection window:
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛABB Switzerland LtdÛÛÛÛÛÛÛÛÛÛÛÛExampleÛÛÛÛÛÛÛÛÛÛÛÛÛREG316*4 Generator TerminalÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛÚEdit Function ParametersÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ¿Û
Û³ ³Û
Û³ Func Nr 2 - Voltage-DT * V> Max Voltage * ³Û
Û³ ³Û
Û³ ParSet4..1 P1 Select ³Û
Û³ Trip B10300000 ³Û
Û³ Delay 02.00 s ³Û
Û³ V-Setting 1.200 UN ³Û
Û³ MaxMin MAX (1ph) Select ³Û
Û³ NrOfPhases 001 ÉA-D Input ChannelsÍÍÍÍÍÍÍÍÍÍ» ³Û
Û³ VoltageInp 6 º º ³Û
Û³ BlockInp f 1 Trip ºÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄ¿º ³Û
Û³ Trip S104 L03 SC1307º³ 1³ 2³ 3³ 4³ 5³ 6³ 7³ 8³ 9³º ³Û
Û³ Start S103 ER º³ c+ c+ c³ c³ v³Xv³ v+ v+ v³º ³Û
Û³ RETURN/ENTER ºÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÙº ³Û
Û³ ºVT 1ph 1.00 º ³Û
Û³ ºV RS, Max Voltage º ³Û
Û³ ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ ³Û
ÛÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛOn - Line 9600 bps SCS:SPAÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛV6.2b | V6.2bÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
Fig. 5.7 “A-D Input Channels” selection window
The nine boxes in the selection window representing the c.t. and
v.t. input channels available are designated as follows:
Top: 1...9 : Channel No.
Bottom: c : c.t.
v : v.t.
o : no input transformer connected
+ : two “+” signs link a three-phase input trans-
former group
X : selected channel.
The input transformer type and any user comment are displayed
in the lower part of the window for the field currently selected.